1. 19 inches standard structure design of rack mount, compact structure and sinusoidal wave output provide best power supply guarantee.
2.0 conversion time between mains mode and battery mode.
3.lt has detection function of input zero line and fire line.
4.Having voltage surge protection function and strong anti-interference function.
5.Equipped with correction function of input power factor
6. Original matching battery.
7.Supporting mobile smart monitoring card , users can realtime monitor every data of the UPS by mobile APP
Model | RTX 1KVA | RTX 1KS | RTX 2KVA | RTX 2KS | RTX 3KVA | RTX 3KS | |
Rated Power | 1kVA/0.9kW | 2kVA/1.8kW | 3kVA/2.7kW | ||||
Input | Voltage Range | 90-285Vac 1P2W+G | |||||
Working Frequency Range | 40-70Hz (settable) | ||||||
Input Power Factor | ≥0.99 | ||||||
Output | Rated Voltage and Accuracy | 220Vac(1±2%) 1P2W+G | |||||
Output Frequency | 46-54Hz synchronize with mains power; 50Hz (Mains power between 40-46Hz and 54-60Hz ); 50Hz(Battery) | ||||||
Rated Current | 4.5A | 9.1A | 13.6A | ||||
Output Power Factor | 0.9 | ||||||
Output Harmonic Wave | ≤4% (Full R load) | ||||||
Crest Factor | 3: | 1 | |||||
Output Overload | Overload pre-warning :100%±2%<Load Output warning:102%±2%≤Load≤110%±2%: Convert to bypass mode and alarm after 30mins; Output warning:110%±2%<Load≤130%±2%: Convert to bypass mode and alarm after 10mins; Output warning:130%±2%<Load≤150%±2%: Convert to bypass mode and alarm after 30s; Convert to bypass mode and alarm after 200ms, Load>150%±2% | ||||||
Conversion time between Mains Power and Battery | 0ms | ||||||
Efficiency | ≥85% | ||||||
Battery | Rated Voltage | 24Vdc | 36Vdc | 48Vdc | 72Vdc | 72Vdc | 96Vdc |
Quantity | 2 | External | 4 | External | 6 | External | |
Charging Current | 1A | 5.5A | 1A | 5.5A | 1A | 5.5A | |
Dimension (LxWxH) mm | 400x482.6x88 | 550x482.6x88 | 400x482.6x88 | ||||
Weight | 10.5kg | 6.5kg | 15.5kg | 7.5k | 22kg | 7.8kg | |
Working Temperature | 0℃-40℃ | ||||||
Working Humidity | 20%-95% (non-condensing) | ||||||
Noise | ≤50dB |