Three-phase input single-phase output RTX31 10KVA-20KVA

Product Features

1.19 inches standard design of rack mount, compact structure

2.Sin wave output provides best power supply guarantee.

3.0 conversion time between mains mode and battery mode.

4.lt has detection function of input zero line and fire line.

5. Having voltage surge protection function and strong anti-interference function

6.Equipped with correction function of input power factor.

7.Supporting mobile smart monitoring card , users can realtime monitor every data of the UPS by mobile APP


Parameter

ModelRTX31 10KSRTX31 15KSRTX31 20KS
Rated Power
10kVA/9kW15kVA/13.5kW20kVA/18kW
InputVoltage Range207-475Vac 3P4W+G
Working Frequency Range40-70Hz (settable)
Input Power Factor≥0.95
OutputRated   Voltage and Accuracy220Vac(1±1%) 1P2W+G
Output Frequency46-54Hz   synchronize with mains power; 50Hz (Mains power between 40-46Hz and 54-60Hz   ); 50Hz(Battery)
Rated Current45A68A91A
Output Power Factor0.9
Output Harmonic Wave≤3%
Crest Factor
31
Output Overload105%±5%Load≤125%±5%: Convert to bypass output and alarm after 1 min;  
    125%±5%
Load≤150%±5%:   Convert to bypass output and alarm after 30s;
    Load
150%±5%: Convert   to bypass output and alarm after 300ms. 
Conversion time between Mains Power and Battery0ms
Efficiency92%
BatteryRated Voltage192Vdc
Quantity16
Charging Current5.5A
Dimension (LxWxH) mm665x482.6x132.5655x482.6x265
Weight23kg34kg35kg
Working Temperature0-40
Working  Humidity20%-95%
Noise≤60dB


Documentation

Questions? Get in touch with our team.

X