Single-phase input single-phase output 3KVA-20KVA

Product Features

1.Advanced DSP digital control technology

2.LCD+LED display

3. WVith output isolated transformer

4.DC cold start function

5.Frequency self-adaptive system

6.Special short-circuit protection design

7. Intelligent mobile monitoring cards are supported to monitor UPS data in real time through mobile apps.

Parameter

ModelTD11 3KVATD11 6KVATD11 10KVATD11 15KVATD11 20KVA
Rated Power
3kVA/2.4kW6kVA/4.8kW10kVA/8kW15kVA/12kW20kVA/16kW
InputRated   Voltage and Range220Vac ±25%
Input Form1P2W+G
Frequency Range40Hz-70Hz (settable)
OutputRated   Voltage220Vac
Output Form1P2W+G
Static Voltage Accuracy±2%
Dynamic Voltage Transient≤9%
Distortion of output voltage waveform≤3%(liner)≤8%(non-liner)
Power Factor0.8
Output Frequency50Hz/60Hz
Output Overload105%±5%≤ Load: Overload warning;
    105%±5%Load≤125%±5%:   Convert to bypass output after 2 mins;                                                        125%±5%Load≤150%±5%:   Convert to bypass output after 30s;
    Load
150%±5%: Convert   to bypass output after 500ms. 
BatteryRated Voltage192Vdc
EnvironmentOperating   Temperature0-40
Operating Humidity20%-95%   (non-condensing)
Dimension (LxWxH) mm533x260x501560x260x717655x370x900
Weight40kg65kg79.5kg122kg152kg


Documentation

Questions? Get in touch with our team.